Product center

undefined
undefined
undefined
+
  • undefined
  • undefined
  • undefined

OM.R960 Circuit Breaker Mechanical Characteristics Online Monitoring System

Intelligent GIS Monitoring Product Series

Product consultation:

  • 产品描述
    • Commodity name: OM.R960 Circuit Breaker Mechanical Characteristics Online Monitoring System

    Product Overview
    The OM.R960 circuit breaker mechanical characteristic online monitoring system employs advanced communication, microprocessor, sensing, and database management technologies to perform real-time, online monitoring of high-voltage circuit breakers during operation. Key parameters monitored include the main circuit current, breaker opening/closing status, spring energy-storage motor current, opening/closing coil current, contact travel—essentially all fundamental characteristics of the circuit breaker mechanism. By analyzing this data, the system can calculate parameters such as opening/closing speed and operating time, enabling an assessment of the high-voltage circuit breaker's operational condition. Additionally, it provides functionalities like current waveform analysis, evaluation of contact wear, and estimation of remaining electrical life.


    Advantageous Features
    ● Record and analyze curves such as operating current, on/off coil current waveforms, stroke characteristic waveforms, velocity profile waveforms, breaking current waveforms, auxiliary switch waveforms, and virtual break point waveforms.
    ● By conducting a comprehensive comparative analysis of the curves (time-displacement curve, operating coil current curve), combined with the factory-standard curves, we can assess changes in mechanical condition and identify emerging trends (such as displacement status, time progression, velocity variations, failure-to-operate events, and unintended tripping).
    ● Satisfy the access switch characteristic auxiliary node signal
    ● The travel sensor features a robust, safety-locking bearing design, with multiple principles available for selection (such as attitude sensors, magnetic offset sensors, laser sensors, etc.)


    System Architecture


    System Parameters

    Number

    Parameter Name

    Unit

    Standard parameter values

    1

    System form or model

    One

    One

    External Distributed

    2

    Monitoring the number of fracture surfaces

    One

    One

    1 or 3

    3

    One-time current (closing/opening) Electric current, energy-storage motor electricity Flow, TA current)

    Measurement Range

    In

    0.05In~20ln

    Measurement accuracy

    %

    ≤2

    4

    Time and speed measurement errors

    %

    %

    ≤2

    5

    Energy-storage motor energy-storage timing accuracy

    Ms.

    Ms.

    ±1

    6

    SOE Resolution

    Ms.

    Ms.

    ≤2

    7

    Device Waveform Data Format

    One

    One

    COMTRADE

    8

    Circuit breaker mechanical system Monitoring parameters

    Circuit breaker operation: Closing and tripping circuit diagram with current waveform

    One

    Possess

    Circuit Breaker Operation Parameter Trend (Comparative Analysis) Curve

    One

    Possess

    Circuit Breaker Operation Records and Statistics

    One

    Possess

    Circuit breaker operating characteristic parameters Over-limit alarm

    One

    Possess

    9

    Circuit breaker electrical life test is conducted Monitoring and Diagnosis

    Circuit Breaker Interrupting Current Curve

    One

    Possess

    Circuit Breaker Electrical Life (Contact Wear) Trend Curve

    One

    Possess

    Typical Circuit Breaker Electrical Life Calculation Information

    (Electrical wear, Σ i²dt)

    One

    Possess

    Circuit breaker operation characteristic parameters – Overlimit alarm

    One

    Possess

    10

    Circuit breaker energy storage system is being conducted. Monitoring and Diagnosis

    Energy storage mechanism operating current, Action Time Information

    One

    Possess

    Energy Storage Mechanism: Daily and Monthly Action Count Statistics

    One

    Possess

    Alarm when the energy storage system malfunctions

    One

    Possess

     

    On-site Case

     