OM.Q542 High-Voltage Live Display Device

Intelligent GIS Monitoring Product Series

Product consultation:

  • 产品描述
    • Commodity name: OM.Q542 High-Voltage Live Display Device

    Product Overview
    The OM.Q542 high-voltage live display device utilizes the principle of electric field coupling between the high-voltage electric field and the sensor to perform non-contact inspection from a safe distance. The device features phase-specific control, incorporating functions such as flashing indication, audible alarm, and self-check capability, while also capable of outputting a forced interlock signal.


    Advantageous Features
    ● Electrical Testing and Error Prevention Integration: Electrical voltage detection indicator + anti-misoperation key interface, electrical interlocking contacts, and various other anti-misoperation interlock interfaces
    ● Technologically advanced: Stable induction signal processing circuit design, with additional techniques such as temperature compensation and filtering; comprehensive self-checking technology.
    ● Safe and reliable: The inductive type does not come into direct contact with energized objects; it is unaffected by the electric fields of adjacent phases or nearby lines, ensuring accurate voltage detection and identification. Additionally, the device features automatic interlock protection in case of malfunction.
    ● Wide range of models, diverse structures: The high-voltage live-display interlocking device can meet users' diverse needs; structurally, it offers both embedded and surface-mounted installation options.
    ● Wide range of applications: The device can be installed in switchgear, ring main units, cubicle substations, GIS switchgear, cable terminations, high-voltage busbars, line earthing switches, and open-type switchgear, among others.


    System Parameters

    Name

    Unit

    Parameters

    Rated Voltage

    kV

    40.5 | 126 | 252  |  363 | 550

    Rated frequency

    Hz

    50

    Working Power

    V

    AC220/DC220/DC110

    Forced Interlock Contact Capacity

     

    AC220V/2A

    Power Consumption

    W

    5

    Power Frequency Withstand Voltage

     

    AC 2000V