OM.R966 GIS Bus Expansion Joint Deformation Online Monitoring System

Intelligent GIS Monitoring Product Series

Product consultation:

  • 产品描述
    • Commodity name: OM.R966 GIS Bus Expansion Joint Deformation Online Monitoring System

    Product Overview
    The busbar is a critical component of GIS, and the expansion joint—a subsidiary device of the busbar—plays a fundamental role in compensating for length adjustments during GIS installation, as well as accommodating thermal expansion and contraction of the busbar sections caused by seasonal and environmental temperature fluctuations during operation. Since the length of the GIS busbar changes with ambient temperature, if the expansion joint fails to function properly due to installation or manufacturing defects, it may lead to deformation and gas leakage at connection points under expansion stress, potentially resulting in severe insulation breakdown of the equipment. Therefore, real-time monitoring of the expansion joint's condition provides essential assurance for the daily maintenance and operation of GIS equipment.


    Advantageous Features
    ● Double-ended bearing force rod design
    ● Universal ball joint design allows for free rotation over a wide angle range, effectively overcoming mechanical clearance errors (up to ±12.5°).
    ● Excellent linearity
    ● Resolution better than 0.01 mm
    ● Long service life, with up to 50 million cycles
    ● Protection rating IP65


    System Parameters

    Electrical Parameters

    Unit

    Numerical values

    Workload Range

    mm

    100

    Electrical Stroke

    mm

    102

    Standard Resistance Value

    3

    Resistance Tolerance

    ±%

    20

    Independent Linear

    %

    0.1

    Repeatability

    mm

    0.01

    Slip brush normal operating current

    μA

    ≤1

    Maximum Current to the Slip Brushes During a Fault

    mA

    10

    Output voltage to input voltage effective temperature coefficient ratio

    ppm/k

    Usually 5

    Operating Temperature Range

    °C

    -30~+100

    Working Humidity Range

    %RH

    0–95 (No Condensation)

    Maximum operating speed

    m/s

    5